Liquiphant FTL31 is a point level switch for liquids. The FTL31 is designed for industrial applications in all industries, mainly the machinery industry. The Liquiphant is used for overfill protection or pump dry-run protection in cleaning systems. The IO-Link capability allows easy parameter setting.

 

Description

Field of application

Liquiphant FTL31 is a point level switch for liquids. The FTL31 is designed for industrial applications in all industries, mainly the machinery industry. The Liquiphant is used for overfill protection or pump dry-run protection in cleaning systems. The IO-Link capability allows easy parameter setting. Compact: – Smallest vibronic sensor in the market Safe: – Continuous self-monitoring -Reliable switching independent of media properties Easy: – No calibration – Plug & play – IO-Link connectivity

Point level switch in compact design with stainless steel housing.
  • Process connections: Threads

  • Temperature: -40 to +150°C (-40 to +302°F)

  • Pressure: -1 to +40bar (-14.5 to 580psi)

  • Surface roughness: 3.2µm

  • Overfill protection and leakage detection WHG, marine approvals, final inspection report

Benefits

  • Designed according to highest requirements to quality and environmental sustainability. The self-monitoring Liquiphant offers safe switching also in case of power supply loss.

  • Independent of changing media properties an accurate switching point is offered. IO-Link reduces costs and complexity due to easy configuration of the devices via engineering tools

  • A real plug & play sensor is offered without any need for adjustment even with changing media. Measurement is unaffected by conductivity, build-up, turbulence, flows or air bubbles

  • No calibration is required, no specific know-how or tools (e.g. software) necessary

  • Robust design made of stainless steel (316L) assures highest durability

  • A modular design offers different process temperatures and the widest variety of process connections and accessories in the market to fit every application

  • No mechanically moved parts, free of maintenance

Additional information

Brand

Endress+Hauser/E+H

Measuring principle

Vibration Liquids

Characteristic / Application

Level switch for liquids and is used in tanks, vessels
and pipes.

Supply / Communication

20 … 253V AC/DC, 2-wire
10 … 30V DC-PNP 3-wire

Ambient temperature

-40 °C … 70 °C
(-40 °F … 158 °F)

Process temperature

-40 °C … 150 °C
(-40 °F … 302 °F)

Process pressure / max. overpressure limit

Vacuum … 40 bar
(Vacuum … 580 psi)

Min. density of medium

>0,7g/cm³
(>0,5g/cm³ optional)

Main wetted parts

316L

Process connection

Threads:
G1/2, G3/4, G1, MNPT1/2, MNPT3/4, MNPT1, R1/2, R3/4, R1

Communication

AC/DC, DC-PNP

Certificates / Approvals

CSA C/US, EAC

Safety approvals

Overfill protection WHG
Leakage

Marine approval

ABS/ LR/ BV/ DNV

Options

Adjustment switching delay
Cleaned from oil+grease,
PWIS free